- Dry contact addressable module
- Two typical form C dry contacts at 24VDC 2A, 125VAC 0.5A
- One simple LED for status indication
- 22.0 to 24.0V for working voltage range of SLC
- Simple and accurate address setting without mechanical switches
- UL listed
Addressable modules

Twin relay module, FRRU004-TRM4


Miniature contact module, FRRU004-MCM
- Input signal addressable module, mini-size
- NFPA Class B (Style B) for IDC
- 5.1kΩ, 1/2W end-of-line resistor for IDC
- 22.0 to 24.0V for working voltage range of SLC
- Simple and accurate address setting without mechanical switches
- UL listed


Single contact module, FRRU004-SCM4
- Input signal addressable module
- One simple LED for status indication
- NFPA Class B (Style B) for IDC
- 5.1kΩ, 1/2W end-of-line resistor for IDC
- 22.0 to 24.0V for working voltage range of SLC
- Simple and accurate address setting without mechanical switches
- UL listed


Dual contact module, FRRU004-DCM4
- Input signal addressable module, two inputs
- One simple LED for status indication
- NFPA Class A (Style D) and Class B (Style B) for IDC
- One address in Class A, two addresses in Class B for IDC
- 5.1kΩ, 1/2W end-of-line resistor for IDC in Class B
- 22.0 to 24.0V for working voltage range of SLC
- Simple and accurate address setting without mechanical switches
- UL listed


Conventional initiating zone module, FRRU004-CIZM4
- Addressable module for conventional detectors
- One simple LED for status indication
- NFPA Class A (Style D) and Class B (Style B) for IDC
- 15.7 to 22.6V output voltage range of IDC
- 5.1kΩ, 1/2W end-of-line resistor for IDC in Class B
- 22.0 to 24.0V for working voltage range of SLC
- Simple and accurate address setting without mechanical switches
- UL listed


Monitored output module, FRRU004-MOM4
- Wet output addressable module
- One simple LED for status indication
- NFPA Class B (Style Y) for NAC
- UL listed with Pot ter/Amseco®, Gentex®, and Cooper Wheelock® syncro-modules and devices
- 24VDC, 2A rating for connected device power (releasing device and NAC)
- 5.1kΩ, 1/2W end-of-l ine res i s tor value for notification appliance
- 5.1kΩ, 1/2W with diode, end-of-line device for releasing device
- 22.0 to 24.0V for working voltage range of SLC
- Simple and accurate address setting without mechanical switches
- UL listed


Short circuit isolator, FQIU004-SCI
- One simple LED for status indication
- Self-restoring LED indication
- 22.0 to 24.0V for working voltage range of SLC
- UL listed


Wet output module 4-circuit, 1 address, FRRJ001A-Y-S
- 1 address with 4 circuits
- Return signal per circuit for device activation confirmation
- Circuits applicable to input signals
- 2A maximum voltage output per circuit
- Dry typical form A contact for return signal
- 24.0V for rated operating voltage of SLC
- Simple and accurate address setting without mechanical switches
- Slim unit


Wet output module 16-circuit, 4-address, FRRJ001A-Y-4S
- 4 addresses with 16 circuits
- Return signal per circuit for device activation confirmation
- Circuits applicable to input signals
- 2A maximum voltage output per circuit
- Dry typical form A contact for return signal
- 24.0V for rated operating voltage of SLC
- Simple and accurate address setting without mechanical switches
- Slim unit


Dry contact module 4-circuit, 1 address, FRRJ001A-Y-SS
- 1 address with 4 dry contacts and 4 inputs
- Return signals or input signals available
- Dry typical form A contact for return signal
- 24.0V for rated operating voltage of SLC
- Simple and accurate address setting without mechanical switches
- Slim unit


Dry contact module, 16-circuit, 4-address, FRRJ001A-Y-4SD
- 4 addresses with 16 dry contacts
- Dry typical form A contact at 30VDC, 2A rating
- 24.0V for rated operating voltage of SLC
- Simple and accurate address setting without mechanical switches
- Slim unit


Addressable module for gas detector, FRRJ001-Y-G
- 1 address with 4 circuits
- 1 gas detector per circuit connectable
- Mode l KP35B for LPG and mode l KN35B for natural gas manufactured by Fuji Electric connectable
- 24.0V for rated operating voltage of SLC
- Simple and accurate address setting without mechanical switches
- Slim unit


Addressable module for initiating device 4-address, FRRJ001-Y-4F
- 4 consecutive addresses per unit
- NFPA Class B (Style B) for IDC
- Nohmi conventional fire detectors compatible
- 24.0V for rated operating voltage of SLC
- Simple and accurate address setting without mechanical switches
- Slim unit


Addressable module for initiating device 16-address, FRRJ001-Y-16F
- 16 consecutive addresses per unit
- NFPA Class B (Style B) for IDC
- Nohmi conventional fire detectors compatible
- 24.0V for rated operating voltage of SLC
- Simple and accurate address setting without mechanical switches
- Slim unit

PRODUCT INQUIRY
Have a question or need more details? Use the button below to contact us.
Get a Quote